Midtherm UV - UV-C Air Purifiers
BBH 2025 Award Winner - Best Patient Safety Initiative

Aintree Hospital CT600 Clinical Study

The CT600 ceiling tile installation at Aintree Hospital won the BBH 2025 Gold Award for Best Patient Safety Initiative. Independent scientific validation by Professor Tony Fisher subsequently demonstrated 84-93% reduction in airborne pathogens across occupied NHS patient rooms.

NHS University Hospitals of Liverpool

Aintree Hospital - Single occupancy patient rooms

Professor Tony Fisher

Independent clinical validation and testing

Award-Winning Results

BBH 2025 Best Patient Safety Initiative

Study Parameters

Room Specifications

  • • Volume: ~62m³
  • • Height: 2.1m
  • • Type: Single occupancy patient room
  • • Existing ventilation: Mitsubishi heat exchanger (80-110 m³/hr)

CT600 Configuration

  • • Capacity: 320-600 m³/hr
  • • Air changes: 10 ACH
  • • Installation: Ceiling tile retrofit
  • • Technology: Coandă-based UVC air scrubber

CT600 Installation at Aintree Hospital

The CT600 ceiling tile units were retrofitted into existing ceiling grids in single occupancy patient rooms, demonstrating minimal disruption and seamless integration with existing hospital infrastructure.

CT600 ceiling tile unit installed at Aintree Hospital

Close-up view of CT600 ceiling tile unit installed in patient room ceiling grid

CT600 in NHS patient room at Aintree Hospital

CT600 unit in situ within NHS patient room environment

Clinical Performance Results

Non-specific CFU (Colony Forming Units) counts per 200 litres of air, measured across four patient rooms with controlled on/off testing (UVC disabled vs. enabled):

Test PeriodRoom #1Room #2Room #3Room #4
UVC Disabled (Baseline)67.5 CFU60 CFU57 CFU54 CFU
UVC Enabled (CT600 Active)10.5 CFU8.5 CFU4 CFU6.5 CFU
Pathogen Reduction84.4%85.8%93.0%88.0%

Average Pathogen Reduction

84-93%

Across all four NHS patient rooms tested

Key Conclusions

Laboratory Biovalidation

In-lab biovalidation confirms a CADR (Clean Air Delivery Rate) of >500m³·hr⁻¹ to the Liverpool Protocol standard

Clinical Effectiveness

In-clinic performance achieves an 88% average reduction in environmental (non-specific) CFU count when used in conjunction with existing ventilation systems

Ease of Retrofit

Simple installation into existing ceiling grid demonstrated - no major building works required, minimal disruption to patient care

ESG Impact

Significant contribution to Environmental, Social, and Governance goals through improved air quality, sustainability, energy efficiency, and cost efficiency

Product Featured in This Study

Interested in the CT600 for your facility?

Cookie Consent

We use essential cookies to ensure our website functions properly. These cookies are necessary for basic site functionality and do not collect personal information. By continuing to use this site, you consent to our use of essential cookies in accordance with GDPR requirements.

We do not use tracking cookies, analytics cookies, or third-party advertising cookies. Your privacy is important to us.